01
Juice flow on the evaporator train
A multiple-effect evaporator concentrates clarified juice by boiling it in successive vessels at falling pressure, each effect heated by the vapour off the one before. Control is a set of interacting level and flow loops, and the juice-side flow is commonly inferred from differential pressure across a primary element. Scale on that element drifts the reading over a campaign, so the loop has to be checkable and re-rangeable in place rather than pulled out.