Standards & Certification
Reading a Rosemount 3051 model code: ranges, output, SIL and manifolds
Decode a Rosemount 3051 model string field by field: measurement type, range codes, HART vs Fieldbus, housing, SIL 2/3 to IEC 61508 and manifolds.
- Written by
- A.N Trader technical team
- Published
- Reading time
- 7 min read
A Rosemount 3051 model string tells you, left to right, what the transmitter measures, over what range, on which protocol, out of what materials, in which housing, and what was bolted on at the factory. Read it properly and you know whether the transmitter in the store matches the loop it replaces; read it carelessly and you order a device that is mechanically correct and metrologically wrong. Everything below comes from Emerson’s Product Data Sheet 00813-0100-4001 Rev TA.
The anatomy of the code
Emerson prints a typical model number under its coplanar ordering table: 3051CD 2 A 2 2 A 1 A B4. Field by field:
| Code | Field and meaning |
|---|---|
3051C | Model — coplanar pressure transmitter |
D | Measurement type — differential |
2 | Pressure range — –250 to 250 inH2O (–621.60 to 621.60 mbar) |
A | Output — 4–20 mA with digital signal based on HART protocol |
2 | Materials — coplanar SST process flange, SST drain/vent |
2 | Isolating diaphragm — 316L SST |
A | O-ring — glass-filled PTFE |
1 | Sensor fill fluid — silicone |
A | Housing and conduit — aluminium, 1/2–14 NPT |
B4 | Option — coplanar flange bracket, all SST, 2-in. pipe and panel |
Options are additive and appear at the end, so a real code usually carries several — M5 for an LCD, T1 for transient protection, Q4 for a calibration certificate. The coplanar platform integrates with manifolds, flow assemblies and level solutions, which is why plants standardise on 3051C even for gage duties.
Measurement type: which 3051 are you looking at
| Model | What it is | Measurement types |
|---|---|---|
3051C | Coplanar pressure transmitter | D differential, G gage, A absolute |
3051T | In-line transmitter, connects direct to process | G gage, A absolute |
Beyond those two, 3051L is the level transmitter — a coplanar sensor with a flanged process connection — and 3051CF the DP flowmeter assemblies: Annubar, compact and integral orifice.
Range codes, and why this is the important digit
The range code sets the sensor’s upper range limit (URL). Accuracy, turndown and stability are all expressed as a percentage of span or of URL, so this digit determines the measurement more than any other in the string.
3051C ranges:
| Code | Differential (3051CD) | Absolute (3051CA) |
|---|---|---|
0 | –3 to 3 inH2O (–7.46 to 7.46 mbar) | — |
1 | –25 to 25 inH2O (–62.16 to 62.16 mbar) | 0 to 30 psia (0 to 2.06 bar) |
2 | –250 to 250 inH2O (–621.60 to 621.60 mbar) | 0 to 150 psia (0 to 10.34 bar) |
3 | –1000 to 1000 inH2O (–2.48 to 2.48 bar) | 0 to 800 psia (0 to 55.15 bar) |
4 | –300 to 300 psi (–20.68 to 20.68 bar) | 0 to 4000 psia (0 to 275.79 bar) |
5 | –2000 to 2000 psi (–137.89 to 137.89 bar) | — |
The gage variant 3051CG shares those upper limits; its lower limits match the differential column at ranges 1 and 2, then become –393 inH2O (–0.97 bar) at range 3 and –14.2 psi (–0.97 bar) at ranges 4 and 5. Range 0 is 3051CD only; range 1 is 3051CD, 3051CG and 3051CF only.
In-line 3051T range codes 1 to 6 set upper limits of 30, 150, 800, 4000, 10000 and 20000 psi — 2.06, 10.34, 55.15, 275.79, 689.47 and 1378.95 bar. Every 3051TG gage range runs down to –14.7 psi (–1.01 bar); the absolute 3051TA reads 0 to X psia over the same six limits.
Do not over-range
The 3051 will calibrate far below its URL — minimum span on a 3051CD range 2 is 1.67 inH2O (4.15 mbar) against a 250 inH2O URL — but published performance degrades as you turn it down. Reference accuracy for a 3051C range 2–4 is ±0.04% of span; for spans tighter than 10:1 it becomes ±(0.015 + 0.005 × URL/Span)% of span. Ambient temperature effect per 50 °F (28 °C) behaves the same way:
| Rangedown | Ambient temperature effect, 3051C ranges 2–5 |
|---|---|
1:1 to 5:1 | ±(0.0125% URL + 0.0625% span) |
5:1 to 150:1 | ±(0.025% URL + 0.125% span) |
Pick the range code whose URL sits just above your maximum working pressure. A range 4 transmitter calibrated to a range 2 duty is a worse instrument than a range 2 transmitter, at the same price.
Emerson quotes installed total performance of 0.14% of span and 10-year stability of ±0.2% of URL at 1:1 to 5:1 rangedown; on 3051CD/3051CG ranges 0–1, stability is ±0.2% of URL for 1 year.
HART, Fieldbus, and what each costs you electrically
| Code | Output |
|---|---|
A | 4–20 mA with digital signal based on HART protocol |
F | FOUNDATION Fieldbus protocol |
W | PROFIBUS PA protocol |
X | Wireless — requires wireless options and engineered polymer housing |
M | Low-power, 1–5 Vdc with digital signal based on HART protocol |
HART (A) operates on 10.5–42.4 Vdc with no load; maximum loop resistance is 43.5 × (power supply voltage – 10.5), and HART communication needs at least 250 Ω. Run that formula before approving a long cable schedule.
FOUNDATION Fieldbus (F) operates on 9.0 to 32.0 Vdc at the terminals, 9.0 to 17.5 Vdc for FISCO, drawing 17.5 mA in all configurations including the LCD. Segment design, not loop resistance, is the constraint.
One thing to know before choosing on specification-sheet grounds: for output codes W and M reference accuracy is ±0.065% span rather than ±0.04%, and total performance for W, F and M is ±0.15% of span rather than ±0.14% — opposite to the assumption that digital is automatically better. On a conventional DCS, A is almost always right.
Housing and conduit
| Conduit entry | Aluminium | Stainless steel |
|---|---|---|
1/2–14 NPT | A | J |
M20 × 1.5 | B | K |
G 1/2 | D | M |
| None — wireless only | P engineered polymer | — |
Match the site gland standard; European practice normally wants B or K.
SIL 2/3 and IEC 61508 — the option you have to ask for
The datasheet’s front page states the 3051 is SIL2/3 certified to IEC 61508. That is a statement about the family; what makes a particular transmitter usable in a functional-safety assessment is an option code:
| Code | What it gives you |
|---|---|
QT | Safety certified to IEC 61508 with certificate of FMEDA |
QS | Prior-use certificate of FMEDA data |
For a safety instrumented function QT is not optional in any practical sense: the assessment needs the FMEDA data, and buying without it means chasing documentation later. QS is the prior-use justification route instead.
Easy to miss: DA0 adds Power Advisory HART diagnostics, detecting degraded loop integrity — on-scale failures caused by the loop, not the process — and Emerson states this capability is itself safety certified. Separately, P9 raises the static pressure limit to 4500 psig (310.26 bar) on 3051CD ranges 2–5.
Hazardous-area certification is a separate field: E8 ATEX flameproof and dust, I1 ATEX intrinsic safety and dust, K8 the ATEX combination; E7/I7/N7/K7 IECEx; E5/I5/K5 FM; C6/I6 CSA; plus combinations such as KB and KD.
Manifold selection
A DP transmitter without a manifold cannot be zeroed, isolated or removed safely, so it is part of the specification. On the model code it appears as an assemble-to option:
| Code | Assembly |
|---|---|
S5 | Rosemount 305 Integral Manifold (3051C) — or 306 Integral Manifold on the 3051T |
S6 | Rosemount 304 Manifold or Connection System (3051C) |
Valve count comes from the manifold’s own model code. The datasheet’s drawings show the coplanar transmitter with a 305RC3 3-valve coplanar or 305RT3 3-valve traditional integral manifold, and the 3051T with a 306 2-valve integral manifold. As a rule:
- Differential (
3051C) — a 3-valve manifold: two isolation valves plus an equalising valve, which lets you zero against equal pressure on both sides without depressurising. A 5-valve arrangement adds vent and test connections. In-line (3051T) — a 2-valve manifold: one isolation, one vent/test. - Integral versus conventional —
305/306manifolds bolt to the transmitter and ship assembled, leak-tested and calibrated as one item; the304is separately piped, and the integral route removes two leak paths.
How to decide, in order
- Differential, gage, absolute or level? Picks
3051C,3051Tor3051L. - Maximum working pressure and the span you need. Take the range code whose URL just covers it; check turndown against the equations above.
- Protocol. HART unless the site already runs a Fieldbus segment. Run the loop-resistance formula against the cable schedule either way.
- Wetted materials — flange, diaphragm, O-ring, fill fluid — from the process.
- Housing and conduit to the gland standard; certification to the protection concept.
QTif it is a safety function — before the order, not during SIL verification.- Manifold — 3-valve for DP, 2-valve for in-line.
Quoting against an existing tag? Send the full model string from the nameplate with the calibrated range and manifold arrangement. That is enough to match a Rosemount 3051 exactly, and it removes the commonest cause of a wrong delivery: the right model, the wrong range code.
Products mentioned
Related guides
-
Selection Guides
How to select a valve positioner: linear vs rotary, smart vs electro-pneumatic
A decision guide to specifying a valve positioner: actuator motion, single or double acting, feedback options, area classification and when smart pays.
-
Comparisons
I/P converters explained: selecting between the YT-930 and YT-940
What an I/P converter does, how the Rotork YTC YT-930 and YT-940 differ on protection concept and supply banding, and why converters fail in service.
-
Troubleshooting
Air preparation for valve positioners: why the filter regulator matters
Instrument-air quality decides whether a positioner holds position. What the YTC manuals require, the fault codes bad air produces, and YT-200 sizing.