An I/P converter turns a 4~20 mA DC control signal into a proportional pneumatic pressure. That is all it does. It has no feedback from the valve, no knowledge of where the stem is, and no way to correct for friction, packing drag or unbalanced process force. If you need the valve to be somewhere, you need a positioner. If you need a pressure that tracks a current — to drive a diaphragm actuator on a slow modulating duty, to feed a legacy pneumatic loop, or to give a pneumatic positioner its input — an I/P converter is the right and much cheaper device.
Rotork YTC offers two, and the choice between them has almost nothing to do with performance.
What is identical, and what is not
Both converters take the same input, produce the same output ranges, pass the same air, and hold the same accuracy figures:
| Figure | YT-930 | YT-940 |
|---|---|---|
| Input signal | 4~20 mA DC | 4~20 mA DC |
| Output, standard | 0.02 ~ 0.1 MPa (0.2 ~ 1.0 bar) | 0.02 ~ 0.1 MPa (0.2 ~ 1.0 bar) |
| Output, multi-range | 0~0.12, 0.04~0.2, 0~0.23 MPa | 0~0.12, 0.04~0.2, 0~0.23 MPa |
| Air consumption | Below 2 LPM (sup. 0.14 MPa) | Below 2 LPM (sup. 0.14 MPa, idle) |
| Flow capacity | 70 LPM (sup. 0.14 MPa) | 70 LPM (sup. 0.14 MPa) |
| Linearity / hysteresis | ±0.5% F.S. / ±0.5% F.S. | ±0.5% F.S. / ±0.5% F.S. |
| Sensitivity / repeatability | ±0.2% F.S. / ±0.3% F.S. | ±0.2% F.S. / ±0.3% F.S. |
Do not choose between these two on output range. The four output bands are the same on both, and a specification that says “we need the 0.04~0.2 MPa version so we must have the YT-940” is based on a difference that does not exist.
Here is what does differ:
| Item | YT-930 | YT-940 |
|---|---|---|
| Protection concept | Intrinsically safe, or non-explosion | Flameproof enclosure |
| Hazardous-area rating | ATEX, IECEx Ex ia IIC T5/T6 Gb, Ex ia IIIC T100 °C/T85 °C Db | Flameproof enclosure — rating per the manufacturer’s certification section |
| Ingress protection | IP66 | Type 4X (FM), IP66 |
| Operating temperature | -30 to 85 °C (-22 to 185 °F) | -40 to 85 °C (-40 to 185 °F) |
| Explosion-proof ambient | -40 to 60 °C (T5); -40 to 40 °C (T6) | -40 to 85 °C (T5); -40 to 75 °C (T6) |
| Loop requirement | Min. 6.0 V at 4 mA; max. 7.2 V at 20 mA | Impedance max. 313 Ω @ 20 mA DC |
| Supply pressure | Standard 0.12~0.16 MPa; max. 0.24 MPa | Four bands: 0.13~0.16, 0.14~0.16, 0.22~0.24, 0.25~0.27 MPa |
| Air connection | (N)PT 1/4 | Rc 1/4 or 1/4 NPT |
| Conduit entry | PF 1/2 (G 1/2) | G 1/2 |
| Housing | Aluminium die-casting | Aluminium, polyester powder coating |
| Weight | 1.6 kg (3.53 lb) | 2.5 kg (5.6 lb) |
Protection concept is the decision
Intrinsic safety and flameproof are two different ways of making the same area safe, and a site normally commits to one of them for its whole installation.
The YT-930 is the intrinsically safe unit: the energy available in the loop is limited, by a zener or galvanic barrier in the marshalling cabinet, to a level that cannot ignite the atmosphere. Field wiring is light, and an instrument can be opened for calibration without a hot-work permit. This is why the YT-930 has such a small voltage budget — a minimum of 6.0 V at 4 mA rising to no more than 7.2 V at 20 mA — which is what lets it sit behind a barrier on a long loop and still work with a conventional controller.
The YT-940 is flameproof: the enclosure is built to contain an internal ignition rather than to prevent one. There is no barrier, the wiring is heavier, and its electrical constraint is a plain loop-resistance one — a maximum of 313 Ω at 20 mA DC, which works out to about a 6.3 V drop at full scale. It is also the model that keeps working at -40 °C and carries the wider flameproof ambient band.
The temperature and ingress differences follow from the construction, and the weight difference — 1.6 kg against 2.5 kg — is the cost of the flameproof casting.
Single acting, double acting, and a question converters cannot answer
Specifications regularly ask for a “double-acting I/P converter”. There is no such thing in either specification sheet, and the reason is structural: an I/P converter has one output port and produces one pressure. Single and double acting is a property of the positioner, which has two output ports and decides how to split air between the two chambers of an actuator.
So:
- Spring-return actuator, direct pressure control. One converter, output piped to the diaphragm casing. This works.
- Double-acting actuator. You need a positioner such as the YT-1000R ordered with the double-acting code, or a reversing relay downstream of the converter. Two converters is not the answer.
- Pneumatic positioner already fitted. The converter feeds the positioner’s signal port, and the positioner does the acting-type work.
Supply banding: the YT-940’s unusual feature
The YT-930 has one standard supply band, 0.12~0.16 MPa, with a minimum stated as 0.2 bar greater than the maximum calibrated output pressure and an absolute maximum of 0.24 MPa (2.4 bar).
The YT-940 can be ordered calibrated for one of four supply bands, up to 0.25~0.27 MPa. That matters on older plant where the instrument-air header is set at a pressure chosen for tools rather than for instruments; ordering the converter for the header you have avoids adding another stage of regulation.
Neither of those numbers is a suggestion. Read the maximum again: 0.24 MPa is 2.4 bar. A plant header at 6 or 7 bar is roughly three times the YT-930’s stated maximum supply pressure. Which brings us to the failure modes.
Why I/P converters fail
In the field, converters rarely fail because the electronics stop working. They fail for four reasons, in roughly this order of frequency:
- Supply pressure above the maximum. These are low-pressure devices with a narrow supply window. Piping one directly off a plant header — or off a regulator whose relief has stuck, or one that has been wound up by someone chasing a slow valve — puts it outside its published range. Every converter needs its own filter regulator, and the set pressure needs to be checked, not assumed.
- Dirty or wet air. The converter’s restriction and nozzle are small. Rotork YTC’s positioner manuals for the same air supply are explicit about what is required: clean, dry air compliant with
ISO 8573-1orISA 7.0.01, dried to at least10 °Cbelow ambient, filtered to 5 micron or smaller, with oil avoided. Compressor oil carry-over is the worst of the three because it does not clear itself — it varnishes. - Loop voltage starvation. On the YT-930, if the barrier, cable resistance and everything else in the loop leave less than
6.0 Vat the converter at 4 mA, it will behave erratically at the bottom of the range and look like a calibration fault. Budget the loop voltage before blaming the device. - Ambient outside the rating. The YT-930 is an
-30 to 85 °Cdevice with a tighter-40 to 60 °Climit at T5 in a classified area; the YT-940 runs to-40 °C. A converter mounted against a hot line or inside an unventilated cabinet in a Karachi summer is being asked to work outside what it was sold to do.
Reading the YT-930 model code
The YT-930 ordering code is short enough to decode at a glance:
| Field | Codes |
|---|---|
| Explosion protection | N non-explosion; I ATEX, IECEx |
| Output pressure | 1 0.02~0.1 MPa; 2 0~0.12; 3 0.04~0.2; 4 0~0.23 MPa |
| Conduit and air connection | 1 G1/2 - PT1/4; 2 G1/2 - NPT1/4 |
| Operating temperature | S |
| Option | 0 none; 1 4~20 mA DC feedback signal |
| Gauge | 0 none; 1 0~0.2 MPa; 2 0~0.4 MPa |
One discrepancy to note: the model-code sheet annotates the S temperature code as -30 ~ 80 °C, while the specification table gives -30 ~ 85 °C. Near that limit, confirm the figure against the certificate for the unit supplied rather than trusting either sheet.
How to decide
- What protection concept does the site work to? Barriers and intrinsic safety, or flameproof enclosures and glands. This settles it, and nothing below overrides it.
- What is the lowest ambient the device will see? Below
-30 °C, only the YT-940 qualifies. - What pressure is the air supply actually at? If it is not near
1.4 barand cannot be regulated to a normal instrument value, the YT-940’s supply banding is worth having. - Check the loop budget on the YT-930 —
6.0 Vat 4 mA has to be there after the barrier and the cable. - Confirm the connection standard —
(N)PT 1/4andPF 1/2on the YT-930,Rc 1/4or1/4 NPTandG 1/2on the YT-940. - Order the filter regulator with it. Both bodies take a directly mounted YT-200 with no interconnecting tube.
Products mentioned
Related guides
-
Comparisons
YT-3300 vs YT-3301 vs YT-3303 vs YT-3350: choosing a Rotork YTC smart positioner
Four Rotork YTC smart positioners on one electronics platform. Housing, mounting side, remote sensor, orifice, switches and certificates compared.
-
Selection Guides
How to select a valve positioner: linear vs rotary, smart vs electro-pneumatic
A decision guide to specifying a valve positioner: actuator motion, single or double acting, feedback options, area classification and when smart pays.
-
Standards & Certification
Reading a Rosemount 3051 model code: ranges, output, SIL and manifolds
Decode a Rosemount 3051 model string field by field: measurement type, range codes, HART vs Fieldbus, housing, SIL 2/3 to IEC 61508 and manifolds.